DA-100
Introduction
DA-100 detects combustible or toxic gas leakage and transmits standard electric current output signal 4 ~ 20mA to be connected with various controllers such as gas leakage warning device (GMS-1000/1500/2000), PLC, DDC, or MMR for individual or integrated gas monitoring system.
Specification
Detection principle | Catalytic, electro-chemical, NDIR, or PID |
Gas sampling | Diffusion type |
Target gas | Please refer to the target gas list. |
Measurement range | %LEL,PPM,%vol |
Response time | Within 20sec, 90%/Full Scale |
Accuracy | ≤±2%/Full Scale |
Sensor displacement | Zero - ≤±1%LEL/6 Month, Span - ≤±1%LEL/6 Month |
Calibration | One-touch auto calibration |
Input power | DC 20~30V |
Output signal | 4~20mA/Full Scale - 2.5km transmission |
Operating temp. & humidity | -30℃~60℃, 5~95% RH (Non-Condensing) |
Signal cable | CVVS & CVVSB 1.5sq x 3 Wire - Shield Type |
Conduit tube | 1/2”or 3/4”PF, NPT |
Installation type | Wall or Pipe Station |
Casing material | Cast Aluminum Alloy |
Explosion-proof approval | EX d IIC T5 - KGS |