DA-500
Introduction
DA-500 detects various combustible & toxic gases leaked from industrial areas for gas producers, gas users, gas reservoirs, gas by-producers, and so on, in order to prevent any accidents in advance. DA-500 converts digital signal into the 4-20mA standard current output signal which can be transmitted to various devices such as PLC, DDC, or recorder to build comprehensive gas monitoring system. Also, DA-500 provides RS-485 communication signal and alarm relay contact. DC 4-20mA standard output signal realizes max 2500m long distance output signal transmission and RS-485 communication signal realizes max 1000m long distance signal transmission.
Specification
Detection principle | NDIR (Nondispersive infrared) |
Gas sampling | Diffusion type |
Target gas | Combustible gas, Toxic gas |
Measurement range | %LEL, PPM, %vol |
Response time | Within 30sec, 90%/full scale |
Accuracy | ≤±2%/Full Scale |
Sensor displacement | Zero - ≤±1%LEL/6 Month, Span -≤±1%LEL/6 Month |
User programmable | Calibration density, detection range |
Input power | DC 20~30V |
Output power | 4~20mA/Full Scale - 2.5km Transmission |
Operating temp.& humidity | -30℃~60℃, 5~95% RH (Non-Condensing) |
Signal cable | CVVS & CVVSB 1.5sq x 3 Wire - Shield Type |
Wire conduit | 1/2” or 3/4” PF, NPT |
Installation type | Wall or Pipe Station |
Exterior material | Cast Aluminum Alloy |
Explosion-proof | Ex d IIC T5 - Korea Gas Safety Corporation |
Output | 2 step- Relay Contact (High/Low) |
Communication output | RS-485 communication output(option) |